Does Pressure Reduction Test have Significant Effect on Evaluating Pressure Management to Reduce Physical Leakage Amount

Wu, Wenyan and Gao, Jinliang and zheng, Chengzhi (2015) Does Pressure Reduction Test have Significant Effect on Evaluating Pressure Management to Reduce Physical Leakage Amount. Procedia Engineering, 119 (2015). pp. 1020-1029. ISSN 1877-7058, ESSN: 1877-7058 (In Press)

[img]
Preview
Text
1-s2.0-S1877705815026673-main.pdf - Published Version

Download (883kB)

Abstract

Physical leakage flow is positively correlated with water head in water supply network (WSN). Index model is applied to engineering of pressure management in which physical leakage flow is expressed as index of average head in WSN. The paper analyzed three aspects involving flow meter measurement error, water head impact, water flow instability. The result shows that the error of this model is unacceptable from the data of pressure reduction measurement with water flow. Pressure reduction test have meaningless effect on evaluating physical losses reduction unless when it was conducted, users stop consuming water.

Item Type: Article
Uncontrolled Keywords: Index model; Physical leakage flow; Pressure management; Pressure reduction test; Water head
Subjects: H100 General Engineering
Divisions: Faculty of Computing, Engineering and the Built Environment
Related URLs:
Depositing User: Professor Wenyan Wu
Date Deposited: 25 Apr 2018 13:00
Last Modified: 25 Apr 2018 13:00
URI: http://www.open-access.bcu.ac.uk/id/eprint/5689